Ohio Association of Plumbing Inspectors

Home Up Contents

07 Code Compare
Updates 07 Code Compare Drawings Code Committee Backflow

 

 

Up

2007 Ohio Plumbing Code

Compared to the

2005 Ohio Plumbing Code

 

Prepared by the

OAPI Code Committee

For a printable version, click here, You must have a PDF reader

 

CHAPTER 1 ADMINISTRATION

Added and Deleted

Section 101.1          The “International Plumbing, second printing, Chapters 2 to 13, as “ published by the “International Code Council, Inc.” with errata and editorial changes provided to the publishers of the Ohio Plumbing Code as of the adoption date of this rule are incorporated fully as if set out at length with substitutions as set forth below.  Is used as the basis of this document and is incorporated fully except as References in these chapters to “this code” or to the “plumbing code” in other sections of the Ohio Administrative Code shall mean the “Ohio Plumbing Code”.

Section 101.2          ..use and inspections of plumbing systems and equipment within building. This code shall also regulate those systems, system components, equipment and appliances specifically addressed herein.

Section 101.3          ..refer to sections 102.0 through 119.1.3 101.2 to 119.1.3 of the building code.

CHAPTER ONE OF THE OHIO BUILDING CODE HAS NOW BEEN ADDED TO OUR PLUMBING CODE IN THIS CHAPTER AFTER 101.4  IN THE 2007 OHIO PLUMBING CODE CHAPTER ONE OF THE OHIO BUILDING CODE WILL  BEGIN HERE.

 

CHAPTER 2

Added and Deleted

Alternative Engineered Design-

…and provides an equivalent level of performance for the protection of public health, safety, and welfare. The system design is not specifically regulated by chapters 3 through 12 in accordance with the requirements of Section 106 of the building code.

 

Approved Agency –

An established and recognized agency regularly engaged in conducting test and/or furnishing follow-up inspection services, when such agency has been approved in accordance with the rules of the board. Approved by the code official and that is regularly engaged in conducting test or furnishing inspection services when such agency has been approved in accordance with the rules of the board.

 

Branch interval –

A vertical measurement of distance, 8 feet more in developed length, between the connections of horizontal branches to a drainage stack. Measurements are taken down the stack from the highest horizontal branch connection.

 

Building Drain –

..extends thirty inches 30 inches

 

Code-

..division level designation number 4101:3 of the Administrative Code.

 

Dead End –

..developed length of two feet  2 feet

 

Designed flood elevation -                                                                                                    

             ..datum specified on the community’s legally …

            

Existing Installations –

Any plumbing system regulated by this code that was legally installed prior to the effective date of this code, or for which an approval has been issued.

 

Flood Hazard Area- 

1. ..subject to a one percent  1-percent….

2...flood hazard area on a community’s flood hazard map or as otherwise legally designated flood hazard map.

 

Flow Control (vent) –

A device installed upstream from the interceptor having an orifice that controls the rate of flow through the interceptor and an intake (vent) downstream from the orifice that allows air to be drawn into the flow stream.

 

Grease Trap –

Deleted

 

Grease Removal Device,                                                                                                     

Automatic (GRD)- A plumbing appurtenance that is installed in the sanitary drainage system to intercept free-floating fats, oils, and grease from wastewater discharge. Such a device operates on a time or event-controlled basis and has the ability to remove free-floating fats, oils and grease automatically without intervention from the user except for maintenance.

 

Gridded Water Distribution system-

A water distribution   system where every water distribution pipe is interconnected so as to provide two or more paths to each fixture supply pipe.

 

Nuisance –

See Public nuisance

 

Potable Water –

…chemical quality requirements of the department of health.  Public Health Service Drinking Water Standards of the regulations of the public health authority having jurisdiction.

 

Power Piping--

…boiler pressure greater that fifteen 15 per square inch.

                                                                                                      

Public Nuisance. –

Any building, structure, or part thereof, constructed, erected, altered, manufactured, or repaired not in accordance with the Ohio Revised Code or the rules of the board ,and any building, structure, or part thereof in there is installed, altered, or repaired any fixture, device, and material, or plumbing , heating, or ventilation system, or electric wiring not in accordance with the Ohio Revised Code or the   rules of the board.  See ORC 3781.11©

 

Sink Service –

Any designated sink so approved for liquid discharge, liquid filling, cleaning, and washing in a facility and installed in a dedicated area or space.

 

Trap

Deleted

 

Vertical Pipe –

…makes an angle of forty-five   45 degrees…

 

Waste Receptor. –

A device for receiving the discharge of a waste pipe or pipes and discharges them by gravity into the sanitary drainage system. Waster receptors include, but are not limited to , floor drains, floor sinks, trench drains, hub drains, standpipes, mop basins, service sinks, and laundry trays.


CHAPTER 3

Added and Deleted

Section 301.3               …in accordance with the requirements of this code And the requirements of the department of the city engineer, in cities having such departments, the boards of health of health district, or the sewer purveyors, as appropriate…                                               

Section 305.6.1            Building sewers shall be a minimum of 24 inches below grade. Building sewers shall be installed below grade with a minimum cover of 24 inches measured from the tip of the sewer pipe to the finished grade.                                             

Section 307.4               Truss members and components shall not be cut, drilled, notched, splices or otherwise altered in any way without written occurrence and approval of a registered design professional. Alterations resulting in the addition of loads to any member (e.g.; HVAC equipment, water heater shall not be permitted without verification that the truss is capable of supporting such additional loading.

Section 307.7               Enforcement of the provisions of this section is the responsibility of the building official defined in Chapter 4101:1-1 of the Administrative Code. Chapter 2 of the building code.

Section 308.5               Hanger spacing – Polypropylene (PP) pipe or tubing 1 inch and smaller –2.67 (32 inches)—10b Polypropylene (PP) pipe or tubing 1 ¼ inches and larger ---4  10b

Section 308.9               Stacks deleted

Section 308.9              Parallel water distribution systems. Piping bundles for manifold systems shall be supported in accordance with Table 308.5 Support at changes in direction shall be in accordance with the manufacture’s installation instructions. Hot and cold water piping shall not be grouped in the same bundle.

Section 309.1               added – Reference to regulations in “CFR Parts 59-77” in this section are adopted pursuant to Section 121.75 and 121.76 of the Revised Code and as referenced in rule 4101:3-13-01 of the Administrative Code under the heading of “FEMA”.

Sections 312 .9 -312.9.1- 312.9.2  CHANGED TO :

312.9 Changed to read – Inspection and testing shall comply with Section 312.9.1 and 312.9.2—added new: 312.9.1 Inspections: Annual inspections shall be made of all backflow prevention assemblies and air gaps to determine whether they are operable. Added new: 312.9.2 Testing: Reduced pressure principle backflow preventer assemblies, double check-value assemblies, pressure vacuum breaker assemblies, reduce pressure detector fire protection backflow prevention assemblies, hose connection backflow preventers, and spillproof vacuum breakers shall be tested at the time of installation, immediately after repairs or relocation and at least annually. The testing procedure shall be performed in accordance with one of the following standards: ASSE 5013, ASSE 5015, ASSE 5020, ASSE 5047, ASSE 5048, ASSE 5052, ASSE 5056, CSA B64.10 or B64.10.1

Section 313                  Equipment efficiencies shall be in accordance with the Chapter 4101:1-13 of the Administrative Code. 13 of the building code.

 

CHAPTER 4

Added and Deleted

Section 403.1               …determined   by the building code. Occupancy classification shall be determined in accordance with the building code. When the actual occupant load will be significantly different then that determined by section 1003.2.2 1004 of the building code, the building official may establish alternative basis for the determining of the occupant load. This alternate basis shall be included in the special stipulations and condition section of the certificate of occupancy issued for the structure pursuant to section 110 of the building code. For handicap accessibility requirements, see “Chapter 11, Accessibility” of the building code.

 

Column #3 – 2005 Group         2007 Occupancy

                       

Column #5 – 2005 footnote h 2007 footnote f

 

                        No. 1:   Assembly (see Sections 403.2, 403.4 and 403.4.1

 

         A-1   A-1d

 

Theaters usually with fixed seats and other buildings for the performing arts and motion pictures. 

 

         A-2   A-2d

         A-3   A-3d

                                                                      

Places of worship and other religious services. Churches without assembly hallsb  

                       

No. 2:  Business (see Sections 403.2, 403.4, 403.6  and 403.4.1)

                       

No. 4:  Structures in which occupants are engaged in work fabricating, assembling assembly or processing of products or materials.

 

                        No. 5:  (Water closets)  1 per patientroomd                       

                                    (Lavatories)  1 per patient roomd 

 

Adult day care and child care  (water closets) 1 per 15, (lavatories) 1 per 15, (bathtub/showers) 1 per 15,  (Drinking r 100  (other) 1 service sink

 

No. 6: Mercantile (see sections 403.2, 403.5 and 403.6  403.4, 403.4.1 and 403.4.2)e

 

No. 7:  guestroom  sleeping unit  R-2  Apartment houses 

R-3  Attached one, two and three-family dwellings (including industrialized units)  Multiple single family dwellings

                                                                    

Footnotes:

c  Toilet facilities for employees shall be separate from facilities for inmates or patients.  This was moved to b. d The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required. This was moved to c.

e  Mercantile occupancies are not required to provide customer facilities when the occupant load is 50 or less.

 

f  Deleted   In each bathroom or toilet room, urinals shall not be substituted for more then 67 percent of the required water closets in assembly and educational occupancies.  Urinals shall not be substituted for more than 50 percent of the required water closets in all other occupancies.

 

g  Mercantile occupancies are not required to provide customer facilities when the occupant load is fifty or less. This became e

 

h  In each bathroom or toilet room, urinals shall not be substituted for more than sixty-seven percent of the required water closets. This was rewritten and called f.

 

403.2. Exceptions:      1. Separate facilities shall not be required for private facilities dwelling units and sleeping units.   

 

2. Separate employee facilities shall not be required in occupancies in which fifteen or fewer people are employed structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or less.

 

Sections 403.4 through 403.8 have been totally revised.

 

Section 403.4:             403.4 Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public use as required in Chapter 29, “Plumbing Systems” of the building code. Access to public facilities shall not be through kitchens, storage rooms, closets or other areas not available to the public. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public facilities.

     

Section 403.4.1           Location of toilet facilities in occupancies other than covered malls. In occupancies other than covered malls, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed 500 feet (152m).

Exception: The location and maximum travel distances to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum travel distances are approved.

 

Section 403.4.2           Location of toilet facilities in covered malls. In covered mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed 300 feet (91 440 mm). In covered mall buildings, the required facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum travel distance to central toilet facilities in covered mall buildings shall be measured from the main entrance of any store or tenant space. In covered mall buildings, where employees” toilet facilities are not provided in the individual store, the maximum travel distance shall be measured from the employee’s work area of the store or tenant space.

 

Section 403.6.2 403.4.3 Pay facilities. Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities.

 

Section 403.7 403.5    Signage

 

Section  403.8  403.6  Enforcement

 

Section  404.1             Where required. The provisions of the building code, “Chapter 11, Accessibility” of the building code shall control the design and construction of facilities for accessibility to physically disabled persons. Enforcement of the provisions of this section is the responsibility of the building official as defined in Chapter two 2 of the building code.

 

Section 405.3.1           Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than fifteen 15 inches (381 mm) from its center to any side wall, partition, vanity or other obstruction, or closer than thirty 30 inches (762 mm) center-to-center between water closets, urinals and adjacent fixtures. There shall be at least a twenty one 21 inches (533 mm) clearance in front of the water closet, urinal or bidet to any wall, fixture or door. Water closet compartments shall not be less than thirty 30 inches (762 mm) wide or sixty 60 inches (1524 mm) deep (see Figure 405.3.1). There shall be at least a twenty one 21 inches (533 mm) clearance in front of a lavatory to any wall, fixture or door (see figure 2903.3.1). See Chapter 11 Accessibility” of the building code this code for minimum required dimensions for accessible fixtures.

 

Section 405.4              Floor and wall drainage connections. …….. or an approved setting compound conforming to FS TT-P 1536a.

 

Section 406.3              Waste connection. ………. Automatic clothes washers that discharge by gravity shall be permitted to drain to a waste receptor or an approved trench drain.

 

Section 407.1              Approval. Bathtubs shall conform to ANSI Z124.1.2, ASME A112.19.1M …..

 

Section 410.1              Approval. Drinking fountains …… ASME A112.19.1M, ASME A112.19.2M, or ASME A112.19.9M, and …… conform to ARI 1010. Drinking fountains and water coolers shall conform to NSF 61, Section 9. Where water is served in restaurants or where bottled water coolers are provided in other occupancies, drinking fountains shall not be required.

 

Section 412.2              Floor drains traps shall have removable strainers. The strainer shall have a waterway area of not less than the area of the tailpiece. The floor drain shall be constructed so that the drain is capable of being cleaned. Access shall be provided to the drain inlet.

 

Section 416.5              Tempered water for public hand-washing facilities. Tempered water shall be delivered from public hand-washing facilities through an approved water temperature limiting device that conforms to ASSE 1070.

 

Section 417.4              Exception Shower compartments having not less than 25 inches (635 mm) in minimum dimension measured from the finished interior dimension of the compartment, provided that the shower compartment has a minimum of 1,300 square inches (.838 m2) of cross-sectional area.

 

Section 419.1              Approvals. Urinals shall conform to ANSI Z124.9, ASME A112.19.2M, CSA B45.1 or CSA B45.5. Urinals shall conform to the water consumption requirements of Section 604.4. Water supplied urinals shall conform to the hydraulic performance requirements of ASME A112.19.6, CSA B45.1 or CSA B45.5.

 

Section 421.2              Installation. Access shall be provided to the pump.

 

Section 421.5              Access to pump. Access shall be provided to circulation pumps in accordance with the manufacturer’s installation instructions. Where the manufacturer’s instructions do not specify the location and minimum size of field-fabricated access openings, a 12-inch by 12-inch (305 mm by 305 mm) minimum sized opening shall be installed to provide access to the circulating pump. Where pumps are located more than 2 feet (609 mm) from the access opening, an 18-inch by 18-inch (457 mm by 457 mm) minimum sized opening shall be installed. A door or panel shall be permitted to close the opening. In all cases, the access opening shall be unobstructed and of the size necessary to permit the removal and replacement of the circulating pump.

 

Section 421.6              Whirlpool enclosure Renumbered

 

Section 424.1.2           Waste fittings. Waste fittings shall conform to ASME A112.18.2, ASTM F 409, CSA B125.1 or one of the standards listed in Table 702.1 and 702.4 for above-ground drainage and vent pipes and fittings, or the waste fittings shall be constructed of tubular stainless steel with a minimum wall thickness of 0.012 inches (0.30 mm), tubular copper alloy having a minimum wall thickness of 0.027 (0.69 mm) or tubular plastic complying with ASTM F 409.

 

Section  424.2             Hand showers. Hand-held showers shall conform to ASSE 1014 ASME A112.18.2 or CSA B125.1. Hand-held showers shall provide backflow protection in accordance with ASME A112.18.1 or CSA B125.1 or shall be protected against backflow by a device complying with ASME A112.18.3.

 

Section 424.3              Individual Sshower valves. Individual Sshower and tub-shower combination valves shall be balanced pressure, thermostatic or combination balanced-pressure/thermostatic valves that conform to the requirements of ASSE 1016 or CSA B125 and shall be installed at the point of use. . Multiple (gang) showers supplied with a single tempered water supply pipe shall have the water supply for such showers controlled by a master thermostatic mixing valve complying with ASSE 1071. Shower and tub-shower combination valves and master thermostatic mixing valves required by this section shall be equipped with a means to limit the maximum setting of the valve to 120°F (49°C), which shall be field adjusted in accordance with the manufacturer’s instructions. In-line thermostatic valves shall not be utilized for compliance with this section.

 

Section 424.4              Hose-connected outlets. Faucets and fixture fittings with hose-connected outlets shall conform to ASME A112.18.3M  Multiple (gang) showers. Multiple (gang) showers supplied with a single-tempered water supply pipe shall have the water supply for such showers controlled by an approved automatic temperature control mixing valve the conforms to ASSE 1069 or CSA B125, or each shower head shall be individually controlled by a balanced-pressure/thermostatic or combination balanced-pressure/thermostatic valve that conforms to ASSE 1016 or CSA B125 and is installed at the point of use. Such valves shall be equipped with a means to limit the maximum setting of the valve to 120°F (49°C), which shall be field adjusted in accordance with the manufacturer’s instructions.

 

Section 424.5              Bathtub and whirlpool bathtub valves. The hot water supplied to bathtubs and whirlpool bathtubs shall be limited to a maximum temperature of 120°F (49°C) by a water temperature limiting device that conforms to ASSE 1070, except where such protection is otherwise provided by a combination tub/shower valve in accordance with Section 424.3.

 

Section 424.4 424.6    Hose-connected outlets. Faucets and    fixture fittings with hose-connected  outlets shall conform to ASME A112.18.3M or CSA B125.

 

Section 424.5 424.7    Temperature-actuated, flow reduction valves for individual fixture fittings.

 

Section 424.6 424.8    Transfer valves.

                                   

Section 425.4              Flush pipes and fittings.1 Flush pipes and fittings shall be of nonferrous material and shall conform to ASME A112.19.5 or CSA B125.

 

Section 425.5              Access to concealed connection. Fixtures with concealed slip-joint connections shall be provided with an access panel or utility space as least twelve inches (305 mm) in its smallest dimension or other approved arrangement so as to provide access to the slip connections for inspection and  


Chapter 5

Added and Deleted

 

Section 501.1                   Exception:. scope of the “Ohio Boiler and Unfired Pressure Vessel” rules..

 

Section 502                      ..Electric water heaters shall conform to the requirements of this code and provisions of the Electrical Code listed in Chapter 13  this code and provisions of Chapter 27 of the building code. Gas-fired water heaters shall conform to the requirement of the “International Fuel Gas Code.”

 

Section 504.6 & 504.6.1 combined    

Requirements for discharge piping. The discharge piping serving a pressure relief valve, temperature relief valve or combination thereof shall:

1. Not be directly connected to the drainage system.

2. Discharge through an air gap located in the same room as the water heater.

3. Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap.

4. Serve a single relief device and shall not connect to piping serving any other relief device or equipment.

5. Discharge to the floor, to an indirect waste receptor or to the outdoors. Where, discharging to the outdoors in areas subject to freezing, discharge piping shall be first piped to an indirect waste receptor through an air gap located in a conditioned area.

6. Discharge in a manner that does not cause personal injury or structural damage.

7. Discharge to a termination point that is readily observable by the building occupants.

8. Not be trapped.

9. Be installed so as to flow by gravity.

10. Not terminate more than 6 inches (152 mm) above the floor or waster receptor.

11. Not have a threaded connection at the end of such piping.

12. Not have valves or tee fittings.

13. Be constructed of those materials listed in Section 605.4 or materials tested, rated and approved for such use in accordance with ASME A112.4.1

 


CHAPTER 6

Added and Deleted

Section 603.2               Exceptions 1. ..conforms to Table 703.1 702.3 .   Exception 3. Deleted

 

Section 604.5               ……The minimum size of individual distribution lines utilized in gridded or parallel water distribution system shall be as shown in Table 604.5.

 

Section 604.10             Gridded and parallel water distribution system manifolds.

 

Section 605.3               …shall have a minimum working pressure equal to the highest available pressure. Water service piping materials not labeled for water distribution shall terminate at or before the full open valve located at the entrance to the structure.  Plastic water service piping shall terminate within 5 feet (1524mm) inside of the point where the pipe penetrates an exterior wall or slab on grade.

 

Section 605.3               TABLE Water Service Pipe

Polyproplene (PP)Plastic pipe or tubing   ASTM f 2389: CSA B 137.11

 

Section 605.4               TABLE Water Distribution Pipe –

CAN standard deleted.

Cross-linked polyethylene/aluminum/high density polyethylene (PEX-AL-HDPE) ASTM 1986.

Polypropylene(PP) plastic pipe or tubing ASTM F 2389;CSA S 137.11

 

Section 605.7               …Ball valves, gate valves, globe valves and plug valves intended to supply drinking water shall meet the requirements of NSF  61.

 

Section 605.17.2          Fittings for cross-linked polyethylene (PEX) plastic tubing as described in ASTM F 877 , ASTM F 1807, ASTM F 1960,…

 

Section 605.21             Polypropylene (PP) plastic. Joints between PP plastic pipe and fittings shall comply with Section 605.21.1.or 605.21.2.

 

Section 605.21.1          Heat –fusion joints. Heat –fusion joints for polypropylene pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion polypropylene fittings or electrofusion polypropylene fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 2389.

 

Section 605.21             PVC Plastics   

 

Section 605.21.2         Mechanical and compression sleeve joints. Mechanical and compression sleeve joints shall be installed in accordance with the manufacture’s instructions.

 

Section 605.21.1 605.22.1       Mechanical joints

 

Section 605.21.2  605.22.2      Solvent Cementing

 

Section 605.21.3  605.22.3      Threaded joints

 

Section 605.22     605.23         Stainless steel

 

Section 605.22.1  605.23.1      Mechanical joints

 

Section 605.22.2  605.23.2      Welded joints

 

Section 605.23     605.24         Joints between different materials.

 

Section 605.23.1  605.24.1      Copper or copper-alloy tubing to galvanized steel pipe.

 

Section 605.23.2  605.24.2      Plastic pipe or tubing to other piping material

 

Section 605.23.3  605.24.3      Stainless steel

 

Section 606.1               Location of full-open valves. 4. On the base of every water riser pipe in occupancies other than multiple-family residential occupancies that are two stories or less in height.       

 

Section 606.2               Location of shutoff valves.

1. On the fixture supply to each plumbing fixture other than in individual guestrooms sleeping units..           

 

Section 607.1               ..In nonresidential occupancies, hot water or tempered water shall be supplied for bathing and washing purposes. Tempered water shall be delivered from public hand-washing facilities. Tempered water shall be supplied through a water temperature limiting device that conforms to ASSE 1070 and shall limit the tempered water to a maximum of 110 F. This provision shall not supersede the requirement for protective shower valves in accordance with Section 424.3

 

Section 607.2               …the hot water supply system shall be provided with a method of maintaining the temperature in accordance with the applicable referenced standard in chapter 13 of the building code.

 

Section 607.2.1            Circulation hot water system piping shall be insulated in accordance with the International Energy Conservation Code. With the applicable referenced standard referenced in Chapter 13 of the building code.

 

Section 608.1               Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Section 608.2 through 608.16.9  608.16.10.

 

Section 608.2               …shall be installed so as to prevent backflow. Plumbing fixture fittings shall provide backflow protection in accordance with ASME A112.18.1.

 

Section 608.13.2          shall conform to ASSE 1013, AWWA C511, or CAN/CSA – B64.3. B64.4 or CSA B64.4.1

 

Section 608.13.5          Pressure-type vacuum breakers shall conform to ASSE 1020 or CSA B64.1.2. and spillproof vacuum breakers shall comply with ASSE 1056..

 

Section  608.13.7         Double check-valve assemblies shall conform to ASSE 1015, CSA B64.5, CSA B64.5.1. or AWWA C510.

 

Section 608.16             Connection to the potable water system shall conform to Sections 608.16.1 through 608.16.9 608.16.10

 

Section 608.16.1          …conforming to ASSE 1022, CSA B64.3.1 or by an air gap. The backflow prevention device and all piping downstream of the backflow preventer must be compatible with carbon dioxide. and all piping downstream of the backflow preventer must be compatible with carbon dioxide.


CHAPTER 7

Added and Deleted

Section 701.1               Scope  …In accordance with Section 3871.03  of the Revised Code, the department of city engineer, in cities having such departments, the boards of health of health districts or the sewer purveyor, as appropriate, shall have complete supervision and regulation of the entire sewage and drainage system of the jurisdiction, including the building sewer and all laterals draining into the street sewers.

 

Section 701.5               Damage to the drainage system. Except where permitted by OEPA wastes detrimental to the public sewer system or to the functioning of the sewer system or to the function of the sewer treatment plant shall be treated and disposed of in accordance with section 1003 requirements of the local sewer purveyor.

 

Section 701.7               Connections. Waste water when discharged into the building drainage system shall be at a temperature not higher than 140EF (60 degrees EC) 140 degrees F (60 degree F)

 

Section 701.8               Engineered systems Sections 103 and 714. Sections 106.7 of the building code and 714.

 

Table 702.2                  Coextruded composite PVC  DWV Schedule 40 IPS pipe (cellular core pipe) ASTM F 891. 

                                    Polylefin pipe CAN/CSA -B181.3 ASTM F 1412 

                                    Polyvinyl chloride ( PVC) plastic pipe (Type DWV) ASTM F 891 

 

Table 702.3                  Concrete pipe CAN/CSA A257.1M, CAN/CSA A257.2M

 

Section 703.1               Where the building sewer is installed within ten 10 feet of the water service, as provided for in Section 603.2, the building sewer pipe shall conform to one of the standards For ABS plastic pipe, cast iron pipe; copper or copper alloy tubing, or PVC plastic pipe listed in Table 702.2. the installation shall comply with the provisions of Section 603.2.

 

Section 705.2.1            CAN/CSA

 

Section 705.5.3            Mechanical joints coupling for hubless pipe and fitting shall comply with CISPI 310, ASTM C 1277 or ASTM C 1540. CAN/CSA

 

Section 705.6               CAN/CSA

           

Section 705.7.1            CAN/CSA

Section 705.8.2            A purple primer that conforms

           

Section 705.15             CAN/CSA

           

Section 705.16.17        is now 705.18.1-7

           

Section 705.17             is now 705.19

           

Section 705.18             is now 705.20

           

Section 705.19             is now 705.21

           

Section 705.20             is now 705.22

 

Section 705.16.1          Heat Fusion Joints                   

           

Section 705.16.2          Mechanical Joints                                

           

Section 705.17             Polyfin plastic                                        

           

Section 705.17.1          Heat-fusion joints                                             

           

Section 705.2               Mechanical and compression sleeve joints.       

           

Section 705.18             Joints between different materials.                    

 

Table 705.18                705.20

 

Table 705.19                705.21

           

Section 706.4               Heel –or –side-inlet quarter bends. Heel-or-side inlet quarter shall be an acceptable means of connection, except where the quarter bend serves a water closet. A low-heel inlet shall not be used as a wet-vent connection. Side-inlet quarter bends shall be an accepted means of connection for drainage, wet venting and stack venting arrangements.

 

Section 708.3.2            Building Sewers                       

           

Section 708.3.3            Change of direction. Cleanouts shall be installed at each change of direction of greater than 45 degrees in the building sewer, building drain or horizontal waste or soil degrees. Where more then one change of direction occurs in a run of piping, only one cleanout shall be required for each 40 feet of developed length of the drainage piping.

 

Section 709.1   Table   Service sink..2dfu..11/2”trap

Urinal, non water supplied..0..5dfu’s

…Note d For SI; 1 inch=25.4mm, 1 gallon=3.785 L (gpf=gallons per flushing cycle).

 

Section 711.1.1            Omissions of vents for vertical stack offsets. [see Table 710.1(1), Column 5

 

Section 711.3 (3)         [Column 4 now Column 5

 

Section 712.2               Full open valves Valves required. A check valve and a full open valve, Exception: In attached one, two and three family dwelling (including industrialized units) In building where the “Residential of Ohio ” applies.

 

Section 715.1               If required by the  “ Ohio Environmental Protection Agency” or the authority having jurisdiction local sewer purveyor a backwater valve shall be installed only for the plumbing fixtures where the flood level rim of the lowest plumbing fixtures are below the elevation of the manhole in the public sewer. Such fixtures shall be protected by a backwater valve installed in the building drain, horizontal branch of the building drain or horizontal branch serving such fixtures.


CHAPTER 8

Added and Deleted

Section 802.1.4            Where wastewater from swimming pools, and  backwash from filters and water from pool deck             drains discharge to the building drainage system, the discharge shall be through an indirect waste pipe by means of an air gap. Water from pool deck drains shall discharge through an indirect waste pipe by means of an air gap or air break.

                                   

Section 802.1.8            DELETED

 

 

Chapter 9

Added and Deleted